Item Details:
This standard describes resilient-seated cast-iron eccentric plug valves,
3 in. (75 mm) through 72 in. (1,800 mm) in diameter, with flanged, grooved, or
mechanical-joint ends, for water, wastewater, and reclaimed water systems having
a pH range from 6 to 12 and a temperature range from 33ºF to...
Back to AWWA C517-09 Resilient-Seated Cast-Iron Eccentric Plug Valves (PDF)
This standard describes resilient-seated cast-iron eccentric plug valves,
3 in. (75 mm) through 72 in. (1,800 mm) in diameter, with flanged, grooved, or
mechanical-joint ends, for water, wastewater, and reclaimed water systems having
a pH range from 6 to 12 and a temperature range from 33ºF to 125ºF (0.6ºC
to 52ºC). The minimum design pressure shall be 175 psig (1,208 kPa) for 3 in.
through 12 in. (75 mm through 300 mm) sizes and 150 psig (1,034 kPa) for 14 in.
through 72 in. (350 mm through 1,800 mm) sizes. Major changes made to the standard in this revision
include the following:
expanded Scope and Purpose to include wastewater and reclaimed water
service;
added references to ANSI/AWWA Standards C541 and C542 for power
actuator requirements; and,
removed contractual language from the body of the standard.